Light and Ventilation Regulation
NATURAL LIGHTING & VENTILATION
NATURAL LIGHTING & VENTILATION
Building/space Type
Window to floor area
Fix Opening to floor area
Building/space Type
Window to floor area
Fix Opening to floor area
Residential
not less 10%
not less 5%
School
not less 20%
not less 10%
Hospital
not less 15%
not less 7.5%
Toilet
not less 5% (adaptable based on number of wc/urinals)
There are no rows in this table
Minimum Size of Air Well
Minimum Size of Air Well
Building Height
Air Well Area (m2)
Minimum Width (m)
Building Height
Air Well Area (m2)
Minimum Width (m)
up to 2 storeys
7
2.5
up to 4 storeys
9
2.5
up to 6 storeys
11
2.5
up to 8 storeys
13
2.5
more than 8 storeys
15
2.5
There are no rows in this table
Minimum Size of Air Well for Toilet
Minimum Size of Air Well for Toilet
Building Height
Air Well Area (m2)
Minimum Width (m)
Building Height
Air Well Area (m2)
Minimum Width (m)
up to 2 storeys
3.5
2
up to 4 storeys
4
2
up to 6 storeys
4.5
2
up to 8 storeys
5
2
more than 8 storeys
5.5
2
There are no rows in this table