Understanding Fire Regulations and Codes:

icon picker
Building Volume

Building Volume is used to calculate the road or space allowing fire engines to approach the building and support the required weight for fire-fighting and life-saving purposes.
UKK 140 Access Requirements:
Width of two-way entrance road not less than 12 meters
Width of fire apparatus access not less than 6 meters
Distance from the edge of the access to the building no more than 2 meters
Fire apparatus access connected to the entrance road
Turning radius not less than 6 meters
Gradient not less than 1:12
Able to support a load of 25 tons
Dead-end access roads longer than 18 meters must have a turnaround area provided

Perimeter Ratio vs Building Volume
Building Volume (cubic meters)
Minimum Perimeter Ratio
7,000 - 28,000
1/6
28,000 - 56,000
1/4
56,000 - 84,000
1/2
84,000 - 112,000
3/4
112,000 and above
Island site
There are no rows in this table

7,000 - 28,000
image.png

28,000 - 56,000
image.png

56,000 - 84,000
image.png
image.png

84,000 - 112,000
image.png
image.png

112,000 and above
image.png

image.png