Share
Explore

HighStar Question


1. Safety Requirements , This Project is for industry and trade. Are there any requirements for the selection of location of the settlement in terms of safety., and are there any policy obstacles to settlement ?

TIP: The requirements for the storage of special warehouse for the production of electrolytes , NMP and other hazardous chemical in this project.


Our existing location ,Amita technology (Thailand), has comply with all law about location of settlement. especially in term of safety. Below are some law details about factory establishment location/building.

Control business establishments which harmful for health Law - Ministry of Public Health
The business establishments which harmful for public health must be located far from religious places, hospitals, educational institutions, nurseries, nursing homes, or any other places that require special public health protection, which must not be in a location that could affect public health.
Controlling business establishments.pdf
81.6 kB

Town and country planning Act
Town and country planning Act defined that industrial and/or warehouse must be located in purple zone.
image.png

Fire Prevention and Suppression in Factory : Ministry of Industry
Factory has storage area for raw material or product that be combustible, with continuous area 1,000 sq.m. or more must install automatic sprinkler system cover entire area.
Storage Area for flammable 14 sq.m. or more must install automatic sprinkler system cover entire area.
Storage area of combustible and flammable must be separated from other area by fire resistance material (At least an hour)
Employer must prepare sufficient water for fire extinguishing to continuously supply water to fire extinguishing equipment for at least 30 minutes.
Employer must install smoke/fire detector and alarm cover entire building.
Factory must be installed fire extinguisher that suitable with fuel. (size and quantity is be specified in Law)
Fire Prevention and Suppression.pdf
232.8 kB


2. Sewage treatment capacity, domestic water discharge, VOC discharge requirement

Our wastewater treatment capacity
622 sq.m./day

Domestic water discharge requirement.
Water discharge quality must not over standard. please see standard of each parameter in Topic (3) (table name : Standard of wastewater discharge)

VOC discharge requirement.
VOC discharge (Air Pollution) must not over standard. you can see standard of each parameter in Topic (3) (table name : Standard of Air pollution)

3. Environmental Protection (Water , Steam , Sound , Slag), waste water discharge implementation level and standards , noise execution standards.

Environmental Protection
Wastewater have 2 methods;
Wastewater treatment plant
Influent : Wastewater form Toilet, Water supply system (Softregen & Backwash), Evaporation system (Effluent)
Effluent : Release to Public canals (คลองข้างวัดเขาดิน) under the control of the Marine Department.
Waste : Sludge cake is sent for disposal by a waste processor (WP) licensed by DIW.
Using Activated sludge (AS) system
Max. capacity 622 m3/day (Present avg. 391 m3/day)
Monitoring : Freq. every week by outsources (ref. เงื่อนไขตามใบอนุญาตเททิ้งหรือระบายน้ำทิ้งลงสู่ลำน้ำสาธารณะ)
image.png
Effluent point
Evaporation system
Influent : Carbon mixing from Mixer, Coater, and Electrolyte mixing process.
Effluent : Feed into the wastewater treatment system to meet standards.
Waste : The sludge (slurry) is sent for disposal by a waste processor (WP) licensed by DIW.
Max. Capacity 24 m3/day (Present 2 m3/day based on Wastewater characteristics)
Monitoring : No

Air pollution
Boiler operation
Treatment system : No because LNG is used as a fuel source, which is clean.
Monitoring
Parameter : TSP, Carbon monoxide, Sulfur dioxide, Nitrogen oxide, Opacity
Sample point : 2 point (Stack of Boiler No.1,2 & Boiler No.3)
Freq. every 6 month by outsources (ref. ประกาศกระทรวงอุตสาหกรรม เรื่อง การจัดทํารายงานชนิดและปริมาณสารมลพิษที่ระบายออกจากโรงงาน พ.ศ. 2558)
LINE_ALBUM_1832567 BE_240318_1.jpg
Boiler stack
Coater and Vacuum oven
Treatment system : using Wet scrubber 2 system by DI water (1 system/side)
Monitoring
Parameter : TSP, Carbon monoxide, Sulfuric acid, Nitrogen oxide, NMP (No standard), TVOC (No standard)
Sample point : 2 point (Stack of Anode & Cathode side)
Freq. every 6 month by outsources (ref. ประกาศกระทรวงอุตสาหกรรม เรื่อง การจัดทํารายงานชนิดและปริมาณสารมลพิษที่ระบายออกจากโรงงาน พ.ศ. 2558)
Waste : NMP high water content (NMP+H2O) feed into the NMP distillation tower in the factory to recycle NMP.
LINE_ALBUM_1832567 BE_240318_60.jpg
VOC stack - Anode side
Electrolyte mixing
Treatment system : using Adsorption 1 system by Activated carbon
Monitoring
Parameter : TVOC (No standard)
Sample point : 2 point (In-out)
Freq. every 6 month by outsources (ref. ประกาศกระทรวงอุตสาหกรรม เรื่อง การจัดทํารายงานชนิดและปริมาณสารมลพิษที่ระบายออกจากโรงงาน พ.ศ. 2558)
Waste : Used activated carbon is sent for disposal by a waste processor (WP) licensed by DIW.
LINE_ALBUM_Stack 2nd 2024_241024_40.jpg
Out
Noise & Sound
Treatment system : No Need (Noise is not over standard)
if there is a significant noise source, noise protection measures will be implemented, such as :
Diesel generator, Air compressor : Closed room with walls covered with sound absorbing material.
Monitoring
Parameter : Noise level, Leq 24 hr., Lmax
Sample point : 2 point (North and south of the factory)
Freq. every 1 year by outsources (ref. ประกาศกระทรวงอุตสาหกรรม เรื่อง การจัดทํารายงานชนิดและปริมาณสารมลพิษที่ระบายออกจากโรงงาน พ.ศ. 2558)
LINE_ALBUM_1832567 BE_240318_19.jpg
North
Waste
Comply with relevant laws i.e.,
Storage
ประกาศกระทรวงอุตสาหกรรม เรื่อง การจัดการสิ่งปฏิกูลหรือวัสดุที่ไม่ใช้แล้ว พ.ศ. 2566
[Inform] ประกาศฯ เรื่อง การจัดการสิ่งปฏิกูลหรือวัสดุที่ไม่ใช้แล้ว พ.ศ. 2566 ข้อ 7 p.3.pdf
1.1 MB
Requirement :
Hazardous and non-hazardous waste must be clearly separated.
The containers must be inspected to ensure they are in a safe condition and must be labeled as specified.
The storage must be adequate, appropriate, and kept clean at all times, with signs and symbols clearly visible for safety.
image.png
Soild waste building
Treatment & Dispose
ประกาศกระทรวงอุตสาหกรรม เรื่อง การจัดการสิ่งปฏิกูลหรือวัสดุที่ไม่ใช้แล้ว พ.ศ. 2566
[Inform] ประกาศฯ เรื่อง การจัดการสิ่งปฏิกูลหรือวัสดุที่ไม่ใช้แล้ว พ.ศ. 2566 p.3-5, 70.pdf
1.1 MB
Taking waste out of the factory for treatment and disposal requires a Aor.Kor.1 license.
Other laws and regulations;
[Inform] ประกาศฯ เรื่อง การนำของเสียออกไปจัดการภายนอกบริเวณโรงงาน พ.ศ. 2566.pdf
344.6 kB
[Inform] ประกาศฯ เรื่อง การอนุญาตให้นำของเสียออกนอกบริเวณโรงงาน พ.ศ. 2566.pdf
617.5 kB
[Inform] ประกาศฯ เรื่อง การแจ้งรายละเอียดแสดงการจัดการสิ่งปฏิกูลหรือวัสดุที่ไม่ใช้แล้ว พ.ศ. 2566.pdf
149.5 kB
[Inform] ประกาศฯ เรื่อง การจัดการของเสียภายในบริเวณโรงงาน พ.ศ. 2566.pdf
696.2 kB
S__104595461_0.jpg
Wastewater discharge standard
Standard refer from 3 department of governments. (However, all have same standard value)
Department of Industrial Works (DIW), Ministry of Industry
ประกาศกระทรวงอุตสาหกรรม เรื่อง กําหนดมาตรฐานควบคุมการระบายน้ําทิ้งจากโรงงาน พ.ศ. 2560
[Standard] ประกาศฯ เรื่อง กำหนดมาตรฐานควบคุมการระบายน้ำทิ้งจากโรงงาน.pdf
45.1 kB
Ministry of Natural Resources and Environment
ประกาศกระทรวงทรัพยากรธรรมชาติและสิ่งแวดล้อม เรื่อง กําหนดมาตรฐานควบคุมการระบายน้ําทิ้งจากโรงงานอุตสาหกรรม นิคมอุตสาหกรรม และเขตประกอบการอุตสาหกรรม
[Standard] ประกาศฯ เรื่อง กำหนดมาตรฐานควบคุมการระบายน้ำทิ้ง.pdf
45.7 kB
Marine Department, Ministry of Transport
ประกาศกรมเจ้าท่าที่ 164/2560 เรื่อง กําหนดมาตรฐานควบคุมการระบายน้ําทิ้งจากแหล่งกําเนิดประเภทโรงงานอุตสาหกรรม นิคมอุตสาหกรรม และเขตประกอบการอุตสาหกรรม
[Standard] ประกาศกรมเจ้าท่า เรื่อง กำหนดมาตรฐานควบคุมการระบายน้ำทิ้ง.pdf
47.9 kB
Standard of wastewater discharge
Parameter
Unit
Department of Industrial Works
Ministry of Natural Resources and Environment
Marine Department
Notes
1
pH
-
5.5-9.0
5.5-9.0
5.5-9.0
Open
2
Temperature
Degree celsius
<= 40
<= 40
<= 40
Open
3
Color
ADMI
<= 300
<= 300
<= 300
Open
4
Total Dissolved Solids (TDS)
mg/L
<= 3000
<= 3000
<= 3000
Open
5
Total Suspended Solids (TSS)
mg/L
<= 50
<= 50
<= 50
Open
6
Biochemical Oxygen Demand (BOD)
mg/L
<= 20
<= 20
<= 20
Open
7
Chemical Oxygen Demand (COD)
mg/L
<= 120
<= 120
<= 120
Open
8
Fat Oil and Grease (FOG)
mg/L
<= 5
<= 5
<= 5
Open
9
Total Kjeldahl Nitrogen (TKN)
mg/L
<= 100
<= 100
<= 100
Open
10
Heavy Metal : Copper (Cu)
mg/L
<= 2
<= 2
<= 2
Open
11
Heavy Metal : Nikel (Ni)
mg/L
<= 1
<= 1
<= 1
Open
12
Heavy Metal : Manganese (Mn)
mg/L
<= 5
<= 5
<= 5
Open
There are no rows in this table
Air pollution standard
Types of factories that must control the release of air pollution into the atmosphere, referring to the announcement of the Ministry of Natural Resources and Environment on the determination of industrial factories as sources of pollution that must be controlled for the release of air pollution into the atmosphere. ​
[Inform] ประกาศฯ เรื่อง กำหนดให้โรงงานอุตสาหกรรมที่จะต้องถูกควบคุมการปล่อยทิ้งอากาศเสีย.pdf
172.3 kB
ประเภทโรงงานลำดับที่ 2, 9, 11, 15, 22, 34, 36, 37, 38, 42, 43, 49, 52, 53, 57, 59, 60, 64, 95, 101
Or according to the conditions of the Factory License as specified.
Standard refer 2 department of governments ;
Ministry of Natural Resources and Environment
ประกาศกระทรวงทรัพยากรธรรมชาติและสิ่งแวดล้อม เรื่อง กําหนดมาตรฐานควบคุมการปล่อยทิ้งอากาศเสียจากโรงงานอุตสาหกรรม
[Standard] ประกาศฯ เรื่อง กำหนดมาตรฐานควบคุมการปล่อยทิ้งอากาศเสียจากโรงงานอุตสาหกรรม.pdf
81 kB
ประกาศกระทรวงทรัพยากรธรรมชาติและสิ่งแวดล้อม เรื่อง กําหนดมาตรฐานค่าความทึบแสงของเขม่าควันจากสถานประกอบกิจการที่ใช้หม้อไอน้ํา
[Standard] ประกาศฯ เรื่อง กำหนดมาตรฐานค่าความทึบแสงของเขม่าควันจาก Boiler.pdf
53.4 kB
Ministry of Industry
ประกาศกระทรวงอุตสาหกรรม เรื่อง กําหนดค่าปริมาณของสารเจือปนในอากาศที่ระบายออกจากโรงงาน พ.ศ. 2549
[Standard] ประกาศฯ เรื่อง กำหนดค่าปริมาณของสารเจือปนในอากาศที่ระบายออกจากโรงงาน พ.ศ. 2549.pdf
84.2 kB
Standard of Air pollution
Parameter
Unit
Source
์No combustion
Combustion
Remark
Total Suspended Particulate (TSP)
2
mg/m3
Boiler / Fuel-based heat sources
- Fuel oil
- Coal
- Biomass
- Other fuel
- - - -
240 320 320 320
General production
400
320
Sulfur dioxide (SO2)
2
ppm
Fuel-based heat sources
- Fuel oil
- Coal
- Biomass
- Other fuel
- - - -
940 700 60 60
General production
500
-
Oxides of nitrogen as
Nitrogen dioxide (NO2)
1
ppm
Fuel-based heat sources
- Fuel oil
- Coal
- Biomass
- Other fuel
- - - -
200 400 200 200
Carbon monoxide (CO)
1
ppm
General production
870
690
Hydrogen sulfide (H2S)
1
ppm
General production
100
80
Hydrogen Chloride (HCl)
1
mg/m3
General production
200
160
Sulfuric acid (H2SO4)
1
ppm
General production
25
-
Xylene
1
ppm
General production
200
-
Cresol
1
ppm
General production
5
-
Antimony
1
mg/m3
General production
20
16
Arsenic
1
mg/m3
General production
20
16
Copper (Cu)
1
mg/m3
General production
30
24
Lead (Pb)
1
mg/m3
General production
30
24
Chlorine (Cl)
1
mg/m3
General production
30
24
Mercury (Hg)
1
mg/m3
General production
3
2.4
Opacity
1
%
Boiler
-
10
Excluding boilers fueled by LPG, NG, Electricity
Remark : The standards of both agencies are the same.
Noise & Sound level standard
Standard come from 3 department of governments :
Ministry of Public Health
ประกาศกระทรวงสาธารณสุข เรื่อง กำหนดค่ามาตรฐานมลพิษทางเสียงอันเกิดจากการประกอบกิจการที่เป็นอันตรายต่อสุขภาพ พ.ศ. 2561
[Standard] ประกาศกระทรวงสาธารณสุข เรื่อง กำหนดค่ามาตรฐานมลพิษทางเสียง พ.ศ. 2561.pdf
80 kB
Ministry of Industry
ประกาศกระทรวงอุตสาหกรรม เรื่อง กําหนดค่าระดับเสียงการรบกวนและระดับเสียงที่เกิดจากการประกอบกิจการโรงงาน พ.ศ. 2558
[Standard] ประกาศกระทรวงอุตสาหกรรม เรื่อง กำหนดค่าระดับเสียงการรบกวนและระดับเสียง พ.ศ. 2548.pdf
60.8 kB
Ministry of Natural Resources and Environment
ประกาศคณะกรรมการสิ่งแวดล้อมแห่งชาติ ฉบับที่ 15 (พ.ศ. 2540) เรื่อง กำหนดมาตรฐานระดับเสียงโดยทั่วไป
[Standard] ประกาศคณะกรรมการฯ ฉบับที่ 15 (พ.ศ. 2540) เรื่อง กำหนดมาตรฐานระดับเสียงโดยทั่วไป.pdf
58.3 kB
ประกาศคณะกรรมการสิ่งแวดล้อมแห่งชาติ ฉบับที่ 29 (พ.ศ. 2550) เรื่อง ค่าระดับเสียงรบกวน
[Standard] ประกาศคณะกรรมการฯ ฉบับที่ 29 (พ.ศ. 2550) เรื่อง ค่าระดับเสียงรบกวน.pdf
72.8 kB
Standard of Noise & Sound level
Parameter
Unit
Ministry of Public Health
Ministry of Industry
Ministry of Natural Resources and Environment
Notes
1
Noise level
dBA
<=10
<=10
<=10
Open
2
Leq 24 hr
dBA
-
<=70
<=70
Open
3
Lmax
dBA
-
<=115
<=115
Open
There are no rows in this table

4. Occupational Health Requirement


Health Checkup
Employer must arrange health checkup for employee who perform work with risk factors :
Within 30 days after start working.
Annual health checkup (Once a year).
Noted : Definition of risk factors are :
Hazardous chemicals as announced by department of government.
Toxic microorganisms which may be viruses, bacteria, mold or other biological agents
Radioactivity
Heat, cold, vibration, atmospheric pressure, light or Noise.
Other environmental conditions which may be hazardous to the health of employees, such as dust, wood dust
Health Checkup Law for Person who work with Risk Factor.pdf
107.1 kB

Workplace Air Monitoring (Chemical)
Employer must arrange concentration of chemical in the air monitoring at workplace and storage area then report result to government department.
In case, concentration of chemical in the air is over standard, employer have to implement elimination or engineering control measures within 30 days.

Working Environment (Lighting , Heat , Noise)
Employer must arrange lighting, heat, noise level monitoring at working area and report to department of government.

5. Energy Consumption index requirement.

I don’t understand this.

6. water supply , power supply , gas supply capacity and energy prices.


Water Supply Capacity
image.png
We have 2 water storage tank :
first tank (water 1,400,000 liters) is reserved for fire water.
second tank (water 1,700,000 liters) for utility system , production and domestic water.
We buy raw water from industrial water resource management company, water would be supply by underground pipe to our water storage tank.
Price of water about 19 THB/Unit

Power supply Capacity
For power supply capacity , We have 2 sources :
Provincial Electricity Authority (PEA)
Substation : Transformer 60,000 KVA, Voltage Level 115 kV
Electricity consumption in 2024 (avg.) 2,444,800.00 kWh/month
Price of Electricity : use rate based on Time of Use (TOU) Tariff
1731546675599.jpg
Peak
Time : 9.00 A.M. – 10.00 P.M. Day : Monday-Friday
Off-Peak
Time : 10.00 P.M. – 9.00 P.M. Day : Monday-Friday
Time : 00.00 A.M. – 12.00 P.M. Day : Saturday-Sunday, National Labor Day, and normal public holidays (excluding compensatory holidays)

Solar rooftop on FB01 building
Capacity 2.849 MW
Electricity consumption in 2024 (avg.) 117,017.59 kWh/month
1731550657977.jpg
Fig. Solar power generation system diagram
Price of Electricity from Solar cell : No

Gas Supply Capacity
For gas supply capacity , We have :
LNG
2 LNG storage tanks in our area (50,000 liters x 2 tanks = 100,000 liters )
Noted : for safety reason , we would fill LNG only 90% of storage tank capacity.
LNG price about 483 THB/MMBTU
LNG consumption in 2024 (avg.) 8,242 MMBTU/year
image.png

Nitrogen
A nitrogen storage tank in our area (50,000 liters)
Nitrogen Price is about 4.19 THB/Nm3
image.png