External wall insulation needs to be carefully considered and specified before installation. The following is an analysis and a suggestion for design.
External INSULATION FOR SOLID WALLS
0
Search
Specification
1
DESCRIPTION
2
The house will need to be insulated from the outside. There is a suggested sequence and specification below but this will need to be agreed with the installer and the client. Thermal bridges detailed below.
3
LOCATION
4
All solid walls to be insulated
5
EXISTING FORM / CONDITION
6
The walls are rendered at the front and rear
7
ESTIMATED U-VALUE
8
Currently 2.06 W/m²K aiming for 0.41 W/m²K
9
ROOF LINE
10
The front of the house has sufficient overhang for the insulation to be fitted underneath. The roofs at the rear of the house are to be extended out to avoid the use of verge trims and allow the use of the green detail below.
There are no rows in this table
Thermal bridges present 2
0
Location
Type of bridge
Mitigation
1
Join with neighbouring house
Linear
design
2
Join with roof of house
Linear
Use green insulation detail below
3
Join with roof of extension
Linear
Use amber insulation detail below
4
Ground level
Linear
Use amber insulation detail below
5
Around windows
small area
slim insulation in reveal
6
Around doors
small area
slim insulation in reveal
7
Bay window
Linear
slim insulation in reveal
There are no rows in this table
7
Count
Thermal bridging details to be used for this project
Roof of house
image.png
Roof of extension
image.png
Ground level
image.png
Around windows and doors
image.png
External-wall-insulation-specification-for-weathering-and-thermal-bridge....pdf